Is this product being sold elsewhere for a lower price?
Please fill in the short form below and we will try to work with our suppliers to match their price or provide an even better deal.
Price match requests are handled by professional sourcing staffs.
If the reported product is identical to the product from Sign-in-Global.us, and lower priced sources are found, prices on product pages will be updated within 48 hours (Mon-Fri) after price match is received.
Could not find the commodity information you want to buy on the website?
Let us know and we will make a deal of it.
All requests are reviewed within 48 hours (Mon-Fri).
The actual process of sourcing for the product might take longer. We can not necessarily always find you need products, but all your needs will be valued.
Refurbished, S&A CW-5200DH Industrial Water Chiller (AC 1P 110V 60Hz) for One 8KW Spindle / Welding Equipment / One 130-150W CO2 Glass Laser Tube Cooling, 0.93HPBuy It Now
Refurbished, S&A CW-5200DH Industrial Water Chiller (AC 1P 110V 60Hz) for One 8KW Spindle / Welding Equipment / One 130-150W CO2 Glass Laser Tube Cooling, 0.93HP
CAUTIONS
We are authorized as "S&A" brand name product agent. All of S&A water chillers are certified with design patent. Counterfeiting is not allowed, Please recognize S&A logo when you purchase S&A water chillers.
Description
CW-5200DH industrial water chillers have been popular for over 16 years with the annual output of 30,000 units.It is designed for cooling the one CO2 glass laser tube under 150W of the laser engraving and cutting machine. (Its emitting rate is higher than 60%.)
Cooling capacity is 1400W.
Have design patent Certificate, CE and RoHS Certificate.
This Water Chiller has been sold largely to Europe, South America, Asia and other markets.
Economic cooling equipment, easy to install and operate, compact and easily movable.
Features:
It is suitable for cooling the laser tube under 150W, and the temperature can be adjusted precisely.
You can choose different models according to local voltage and frequency.
It can extend the using life of laser tube and ensure the engraving effect better.
With completed water flow and over high temperature alarm functions
It can control the water temperature, precision is ±0.3℃, which provide stable working conditions for laser devices.
Multiple alarm function: compressor time-delay protection, compressor overcurrent protection, water flow alarm and over high / low temperature alarm;
This series of water chillers adopt intelligent controller, which need not adjust the control parameters under normal
circumstances, it will automatically adjust control parameters according to room temperature changes, to meet the cooling requirement.
CW-5200 water chiller has unique low flow alarm protection function, which ensures the cooling water cycle working safely.
Specific disconnection alarm securing protection.
Enclosed water tanks, water used for a long time.
Equipped with alarm output port, can quickly protect sensitive components.
High cost performance, low failure rate.
Multiple power specifications; CE approval; REACH approval; RoHS approval.
SPECIFICATION
Model
CW-5200DH
Voltage
AC 1P 110V
Frequency
60Hz
Current
0.45~5.7A
Compressor power
0.68KW
0.93HP
Nominal cooling capacity
5186Btu/h
1.52KW
1307Kcal/h
Refrigerant charge
350g
Pump power
0.05KW
Pump lift
12M
Pump flow
13L/min
N.W
26Kgs
G.W
29Kgs
Refrigerant
R-22/R-410a
Precision
±0.3℃
Reducer
Capillary
Protection
Overcurrent protection for compressor, flow alarm, over temperature alarm
Tank capacity
6 L
Inlet and outlet
External Ø10mm brass connector
Ø10mm speedy connector
Dimension
58X29X47 cm (L X W X H)
Package dimension
70X43X58 cm (L X W X H)
CONTOUR AND PARTS INTRODUCTION
Independent production of sheet metal
High precision temperature control system.
Adopt IPG fiber laser for welding and cutting sheet metal.
Temperature control accuracy can reach ±0.3℃.
Ease of moving and water filling
The firm handle can help move the water chillers easily.
Inlet and outlet connector equipped
Multiple alarm protection.
The laser will stop working once it receives alarm signal from the
water chiller for protection purpose.
Cooling fan of famous brand installed
Level gauge equipped.
Adopt SAN JU cooling fan with high quality and low failure rate.
Customized dust gauze available and easy to
take apart
Temperature controller panel description:
The new T503 intelligent temperature controller does not need to adjust the controlling parameters under normal circumstance. It will self-adjust controlling parameters according to room temperature for meeting equipment cooling requirements.
User also can adjust the water temperature as needed.
Temperature controller panel description:
Indicators D1, D2 (as shown) of thermostat working state
D1 ON: thermostat works in intelligent control mode;
D1 OFF: thermostat works in temperature control mode;
D1 FLASHES: thermostat works in parameters setting mode or displays value of room temperature;
D2 ON: chiller works in refrigerating state;
D2 OFF: chiller works in the insulation working state;
D2 FLASHES: chiller works in the energy-saving state;
Press ▼ button will show the room temperature, 6 seconds later to display the restore defaults.
(Meanwhile, D1 is flashing, displaying room temperature.)
▲▼ keys are for adjusting the display status of the controller, parameters selection and adjustment.
RST key: enter key.
SET key: function setting key.
How to set the water temperature of the chiller?
Alarm function
(1) Alarm Display:
When alarm occurs, the error code and the temperature will be alternately displayed.
(2) To suspend the alarm:
In alarming state, the alarm sound could be suspended by pressing any button, but the alarm display remains until the alarm condition is eliminated.
In order to guarantee the equipment will not be damaged while cooling water circulation is out of control, CW-5000/5200series chillers possesses an unique low flow alarm protection.
(1) Flow alarm output ports and the wiring diagram
(2) Flow alarm causes of circulating cooling water and working state
Note: The flow alarm is connected to the normally open relay and normally closed relay contacts, requiring operating current less than 5A, working voltage less than 300V.
Application
Chiller CW-5200 for 150W metal laser cutting machine
Water chiller CW-5200 for acrylic co2 laser cutting machine
Industrial chiller CW-5200 for laser cutter
Air cooled chiller CW-5200 for co2 laser cutting & engraving machine
Water cooled chiller CW-5200 for uv laser marking machine
CW-5200 chiller for 8w-15w uv laser machine
Refrigeration water chiller CW-5200 for laser marking machine
Compressor water chiller CW-5200 for UV curing system printer
Industrial water chiller CW-5200 for laser marker
Certificate
Warehouse
Test System
Packing
Delivery
Installation
Open the package to check if the machine is intact and all the necessary accessories are completed.
Open the injection port to feed cooling water. (Do not let the water spill over!)
Observing the water level gauge and adding water slowly, be careful not to have the water overflowed! For the cooling of carbon steel equipment, the water should be added an appropriate amount of cooling water additive (anti-corrosion water aqua). Working in cold north area, it’s better to use noncorrosive antifreeze fluid.
According to system conditions, please connect the water inlet and outlet pipe well.
Plug in power, turn on the power switch. (Do not start up without water in the water tank!)
(1) Power switch turned on, the circulation pump of the chiller starts working. The first time of operating may cause more bubbles in the pipe leading to a flow alarming occasionally, but running for a few minutes later, it will go back to normal.
(2) After the first boot, you must immediately check whether the water pipe leaks.
(3) Power switched on, if the water temperature is below the set value, it is normal that fans and other components of the machine do not work. The temperature controller will automatically control the working conditions of the compressor, magnetic valve, fans and other parts based on the set controlling parameters.
(4) As it takes a longer time to start over the compressor and other components, according to different conditions, the time is range from seconds to minutes, so do not turn off the power and again on frequently.
Check the water level in the water tank.
The first startup of the new chiller empties the air in the water pipe, leading a slight water level decline, but in order to keep the water level in the green area, it’s allowed to add adequate water again. Please observe and record the current water level, and inspect it again after the chiller running for a period of time, if the water level drops obviously, please re-inspect the water pipeline leakage.
Adjust parameters of temperature controller.
CW-5000/5200 series use an intelligent thermostat. Normally users do not need to adjust it. If it is really necessary, please refer to page 15, “Operating status and parameters adjustment.”
Cautions
Please ensure that the power supply and electrical outlet are in good contact and the earth wire must be firmly grounded!
Please make sure there is stable and normal voltage for the working chiller!
As the refrigeration compressor is more sensitive to the power supply and voltage, so the operating voltage of our standard product is of 210 ~ 240V (110V model is of 100 ~120V). If you do need a wider operating voltage range, customization is available for us.
Unmatched power frequency can cause the chiller damage!
Please choose model of 50Hz or 60Hz according to actual circumstance.
To protect the pump, it’s strictly forbidden to run the chiller without water in the storage water tank!
The new machine is packed after draining whole water in the tank, so please make sure the tank has water inside before machine starting, otherwise it’s easily to have the pump damaged. When the water level is below the green (NORMAL) range of the water level gauge, the cooling capacity of our chiller will go down slightly. Hence please ensure the water level is within the green (NORMAL) range. To drain through circulating pump is strictly prohibited!
Please be sure that the air inlet and air outlet are in good ventilation!
There must be at least 30cm from obstructions to the air outlet which is in the back of the cooler, and should leave at least 8cm between obstructions and the side air inlet.
The filter screen must be regularly cleaned!
It’s essential to unpick and wash the dust gauze, or the serious blockage will cause breakdown to the chiller.
Please pay attention to the effect of the condensate water!
With greater ambient humidity, when the water temperature is lower than the ambient temperature, the condensate water will generate on the surface of water circular pipes and the cooled components. If above circumstance appears, it is recommended to set a higher water temperature or keep pipes and cooled parts warm.
Professional use only!
The appliance is not to be used by children or persons with reduced physical,sensory or mental capabilities, or lack of experience and knowledge,unless they have been given supervision or instruction,children being supervised not to play with the appliance!
Troubleshooting
Failure
Failure Cause
Approach
Machine turned on but unelectrified
Power cord is not plugged in place
Check and ensure the power interface and the power plug is plugged in place and in good contact.
Fuse burnt-out
Pull out the fuse box from the power supply interface of the chiller, check the fuse, replace with spare fuse if necessary and check whether the power supply voltage is stable; Check and ensure the power interface and the power plug is plugged in place and in good contact.
Flow Alarm (panel red light is on)use a water pipe directly connect to the water outlet and inlet but still without water flowing
Water level in the storage water tank is too low
Check the water level gauge display, add water until the level shown in the green area; And check whether water circulation pipe leaks.
Flow Alarm occurs while running with other equipment (panel red light is on),but there is water flowing and no alarm when use a water pipe directly connected to the chiller water outlet and inlet.
Water circulation pipes are blocked or a pipe bending deformation.
Check water circulation pipe
Ultra-high temperature alarm
Blocked dust gauze, bad thermolysis
Unpick and wash the dust gauze regularly
Poor ventilation for air outlet and inlet
To ensure a smooth ventilation for air outlet and inlet
Voltage is extremely low or astable
To improve the power supply circuit or use a voltage regulator
Improper parameter settings on thermostat
To reset controlling parameters or restore factory settings
Switch the power frequently
To ensure there is sufficient time for refrigeration (more than 5 minuets)
Excessive heat load
Reduce the heat load or use other model with larger cooling capacity
Alarm for ultra-high room temperature
The working ambient temperature is too high for the chiller
To improve the ventilation to guarantee that the machine is running under 40℃.
Serious problem of condensate water
Water temperature is much lower than ambient temperature, with high humidity
Increase water temperature or to preserve heat for pipeline
Water drains slowly from outfall during water changing
Injection port is not open
Open the injection port
S&A CW-5200DH Industrial Water Chiller (AC 1P 110V 60Hz) for One 8KW Spindle or Two 100W CO2 Glass Laser Tubes Cooling, 0.93HP
Model
CW-5200DH
Power Supply
AC 110V, 60Hz
Current
4.5~6.5A
Compressor Power
0.68KW
0.93HP
Refrigerating Capacity
5186Btu/h
1.52KW
1307Kcal / h
Refrigerant
R-22 / R-134a / R-410a
Refrigerant Charge
350g
Precision
±0.3℃
Tank Capacity
6L
Reducer
Capillary
Protection
Over current protection for compressor, flow alarm, over temperature alarm
Pump Power
0.03KW
Maximum Flow
13L / min
Maximum Pumping Lift
12M
Inlet and Outlet
External Φ10mm brass connector
Net Weight
26kg
Gross Weight
29kg
Product Dimension
22.8" x 11.4" x 18.5" (580 x 290 x 470mm)
Package Dimension
27.6" x 16.9" x 22.8" (700 x 430 x 580mm)
Alarm function
E1
E2
E3
E4
E5
Over high room temperature
Over high water temperature
Over low water temperature
Room temperature sensor failure
Water temperature sensor failure
Remark:
When alarm occurs, the error code and the temperature will be alternately displayed.
In alarming state, the alarm sound could be suspended by pressing any button, but the alarm display
remains until the alarm condition is eliminated.
Thermostat parameters list:
Order
Code
Project Setting
Range
Factory
Setting
Notes
1
F0
Temperature setting
F9 – F8
25
Constant temperature control effecting
2
F1
Temperature difference values
-15 - +5
-2
Intelligent control effecting
3
F2
Cooling hysteresis
0.1 – 3.0
0.8
4
F3
Way of control
0 - 1
1
1: intelligent
0: constant temperature
5
F4
Alarm for over high water temperature
1 - 20
10
6
F5
Alarm for over low water temperature
1 - 20
15
7
F6
Alarm for over high room temperature
40 - 50
45
8
F7
Password
00 - 99
8
9
F8
The allowed highest water temperature
F0 - 40
30
10
F9
The allowed lowest water temperature
1 – F0
20
Wooden Box: There is total one carton box.
Machine Dimension
22.8" x 11.4" x 18.5" (580 x 290 x 470mm)
Machine Weight
57.2ib (26kg)
Package
Carton box
Packing Size
27.6" x 16.9" x 22.8" (700 x 430 x 580mm)
Gross Weight
63.8ib (29kg)
Packing list:
CW-5000 water chiller machine
1 set
Power cable
1 pc
Connection hose
1 pc
Sealing washer
2 pcs
250V/2A spare fuse
(Mounted on the power socket
interface within the insurance reserve)
1 pc
User manual
1 pc
Alarm signal output plug
1 pc
cooling water additive
1 / 0 bottle
P.S.: cooling water additive is forbidden by express company, so we could not put it into the package. You can buy it from local. Caution: The appliance is not to be used by children or persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge, unless they have been given supervision or instruction, children supervised not to play with the appliance!
Package:
Note: The Water Chiller is ordering production, need 3 to 5 days of stock up time.
User manual for CW-5000 CW-5200 series water chiller
Two-year Comprehensive Warranty for the Equipment & Machine of Sign-in-Global.us Sign-in-Global.us guarantees that all the products are qualified in quality and the technical specifications have reached the factory inspection of OQC (Outgoing Quality Control).
(1) The entire body of all equipment or machines (except consumables) we sell is provided with a 2 - year warranty.
(2) Maintenance methods in which two options (either - or) available for the buyer: · Normal: The buyer sends back a problematic part and Sign-in-Global.us will identify whether repair or change a new one. · Urgent: The buyer purchases a replacement and meanwhile sends back the problematic part, and then Sign-in-Global.us will identify and decide whether refund the replacement.
(3) The Start Time of Warranty: Once such an equipment is shipped out.
(4) For maintenance service, please provide the invoice of purchase order (on which it indicates the equipment or machine model number, name and sold date), equipment or machine serial number, trouble or breakdown description, and better attach photo (s) or video (s).
(5) The purchase order PI is the essential proof for maintenance which ensures your legal interest and right. Please keep it properly after purchase. Additional announcement, the following situations are not covered by the 2-year warranty:
(1) Any product or commodity which was not sold out by Sign-in-Global.us (The model number and serial number are not issued by Sign-in-Global.us)
(2) Any unauthorized repairing, mistake in use, damage, negligence, misuse, accident, change or modification, quality problem caused by incorrect installation; (3) Tearing up or modifying of the label or the serial number of such an equipment or machine; (4) Normal consumption or wearing off such nature usage, wearing down or aging of the cover or shell, plugging or socketing part or unit, etc; (5) The using environment (temperature & humidity) did not match up the requirement specified in the manual or instruction document;
(6) The trouble or breakdown caused by incorrect operation or failure in following the operation instructed in the manual or instruction document; (7) The parts or software not purchased from Sign-in-Global.us; (8) The wearing or vulnerable part; (9) The breakdown or damage caused by nature disaster or force majeure (Such as earthquake, fire, flood, typhoon, thundering, etc). For Receiving Equipment or Machine:
Normally, we will provide you the pictures of equipment or machine and its packing before shipping in order to proof such item in good condition without damages. When you receive it, suppose you find damage on external packing, instead of signing acceptance, please open it first and check the item inside the packing if there is any damage. If you find damage, you can definitely refuse signing acceptance and then claim loss from the express service company. At the same time, please take photos of the damaged packing and item, and contact us (Either our sales consultant whom you know or send email to “service@sign-in-global.us”). Hence, our people will assist you in handling such dispute
Customer Reviews
Love it! Rate it!
Simply write a review of a product and you can get up to 500 Points (Equivalent to $5) for Next Orders.
≥ 120 words + ≥ 3 clear photos = Up to 1000 Points (Equivalent to $10).
Show us why you love or how to use the product. Help other shoppers find the right product!